Features: | |
| Compliance | Standards: EN 60079-0, EN 60079-30-1 |
| Approvals | IECEx, ATEX |
| Rugged construction | Outer Metallic sheath makes it robust and suited to hostile conditions. |
| Fire Resistance | The magnesium oxide (MgO) insulation in TMIC cables is non-combustible, providing a high level of fire safety. |
| Custom built | We also offer custom designs of a product to suit individual requirements. We can design for various dimensions and voltages |
Depending on the application and site conditions (viz. temperature, weather conditions, chemical environment), we can offer options of various insulating materials for TMIC to match your individual requirements.
Specifications: | |
| Maximum Rated Voltage | 600Vac for assembled unit & 750Vac for cold lead cables. |
| Minimum Bending Radius | Minimum Six times the cable cross sectional diameter. |
| Ambient Temperature | -65 Deg.C to +55 Deg.C |
| Maximum Maintenance Temperature | +500 Deg.C |