 Specifications

Compliance Standard: IEC 60800, IEC / EN 62395-1 and VDE 0721-52.
Approvals SGS Fimko & EAC.
Standard Power output at 10°C on Pipe @230 V a.c 10, 15, 20, 25 & 30 W/m.
Min. Installation Temperature -40° C.
Operating Temperature – Switched on Max 65° C.
Operating Temperature- Switched off Max 85° C.
Minimum Bending Radius 25mm.
Circuit Breaker Max. 16 A.

#TDIT-SR is available in factory terminated standard lengths: 5, 8, 10, 12, 15, 20, 25, 30, 35, 40, 50, 60 and 70 m.

Range

Type Nominal output Nominal Dimensions
TDIT-SR-10-AZ 10W/m @ 10OC 10.50 mm x 5.5 mm
TDIT-SR-10-BZ 10W/m @ 10OC 10.00 mm x 5.6 mm
TDIT-SR-15-AZ 15W/m @ 10OC 10.50 mm x 5.5 mm
TDIT-SR-15-BZ 15W/m @ 10OC 10.00 mm x 5.6 mm
TDIT-SR-20-AZ 20W/m @ 10OC 10.50 mm x 5.5 mm
TDIT-SR-20-BZ 20W/m @ 10OC 10.00 mm x 5.6 mm
TDIT-SR-25-AZ 25W/m @ 10OC 10.50 mm x 5.5 mm
TDIT-SR-25-BZ 25W/m @ 10OC 10.00 mm x 5.6 mm
TDIT-SR-30-AZ 30W/m @ 10OC 10.50 mm x 5.5 mm
TDIT-SR-30-BZ 30W/m @ 10OC 10.00 mm x 5.6 mm

Circuit breaker selection chart

Heating circuit length (m) with Type C circuit Breaker
TDIT-SR-10 TDIT-SR -15 TDIT-SR -20 TDIT-SR -25 TDIT-SR -30
Circuit Breaker size (Amps) 10 16 10 16 10 16 10 16 10 16
Switch-on temperature (°C) +10OC 122 135 90 115 72 100 60 92 52 84
-15 OC 105 125 70 100 57 91 46 75 40 63
-30OC 86 110 62 93 52 84 41 68 36 57